A Comparison of Ceiling Jet Temperatures Measuremed in an Aircraft Hanger Test Fire with Temperatures Predicted by the DETACT-QS and Lavent Computer Models
Auteur : W. Douglas Walton, Kathy A. Notarianni
Date de publication : 1993
Éditeur : National Institute of Standards and Technology
Nombre de pages : 29
Résumé du livre
Predictions of the DETACT-QS and LAVENT computer fire models are compared to temperature measurements made during the calibration of the fire detection system in a military aircraft hanger. Two 3.34 m2 isopropyl alcohol pool fire tests of 60 second duration were conducted in the 37 m by 40 m by 14 m high main hanger bay. Brass disks with a known thermal response time index (RTI) were used to simulate the thermal element in a sprinkler or heat detector. Measurements were made of centerline plume temperatures, and ceiling jet gas and disk temperatures at radial distances of 0, 2.7, 5.5, 8.2, and 11.0 m from the centerline of the fire, 380 mm below the ceiling. At a radial distance of 5.5 m, measurements of ceiling jet gas temperatures were also made 150 and 610 mm below the ceiling. Comparisons of predictions and measurements demonstrate some of the strengths and weakness of DETACT-QS and LAVENT for this fire scenario.